Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/10/2007

Applicant:

J H ASSOCIATES LLC

Description:

Full fire inspection done by Inspector John Bieg on 9/7/07.

Outstanding Inspections

Case Number: T07FR01757
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
09/10/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2 Storage in the workshop shall be orderly. A RE-INSPECTION IS SCHEDULED FOR 9-21-07.
09/10/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 504.2 Remove the NOT AN EXIT SIGN, from the exterior door located on the northwest side of the workshop.
09/10/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 505.1 Replace the missing building address numbers.
09/10/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 507.1 Hazards to fire fighters. The sump lid shall be closed when not being used.
09/10/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.1 The northwest exit door shall have an approved illuminated exit sign posted above the door.
09/10/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3 The southwest exit sign located in the workshop shall be illuminated.
09/10/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 All exit sign shall have emergency back up power.
09/10/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.2 All egress doors located in the workshop shall be free from obstructions.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01757
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/23/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected.