09/04/2007
Applicant:
ADAMS RICHARD W & ELIZABETH CP/RS
Description:
Inspection per Group home check list.
Outstanding Inspections
Case Number: T07FR01726
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 8
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/04/2007 | INSP - FULL | DRAMIREZ | Correction Required | Assisted living group home, licensed for 10 |
| 09/04/2007 | VIOL - ADMINISTRATION | DRAMIREZ | Correction Required | IFC 102.3 Provide and post C of O |
| 09/04/2007 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Correction Required | IFC 605.1 Provide cover plates for electrical outlets in following areas: 1.) laundry room 2.) in bdrms. #3 & #4 3.) main electrical panel,exterior, east side |
| 09/04/2007 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Correction Required | IFC 605.5 Extension cords shall not be a substitute for permanent wiring. 1.) main room, SE corner. 2.) laundry room. |
| 09/04/2007 | VIOL - FIRE PROTECTION SYSTEMS | DRAMIREZ | Correction Required | IFC 901.6.2 Provide smoke alarm testing records. |
| 09/04/2007 | VIOL - FIRE PROTECTION SYSTEMS | DRAMIREZ | Correction Required | IFC 907.2.10 Replace smoke alarm in pantry area and service smoke alarm in kitchen area. |
| 09/04/2007 | VIOL - MEANS OF EGRESS | DRAMIREZ | Correction Required | IFC 1027.2 Service eegress windows to allow them to open more readily. |
| 09/04/2007 | VIOL - MEANS OF EGRESS | DRAMIREZ | Correction Required | IFC 1027.3 Provide clear path, exit discharge, from emergency eegress windows, west side. |