Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

09/04/2007

Applicant:

ADAMS RICHARD W & ELIZABETH CP/RS

Description:

Inspection per Group home check list.

Outstanding Inspections

Case Number: T07FR01726
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
09/04/2007 INSP - FULL DRAMIREZ Correction Required Assisted living group home, licensed for 10
09/04/2007 VIOL - ADMINISTRATION DRAMIREZ Correction Required IFC 102.3 Provide and post C of O
09/04/2007 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Correction Required IFC 605.1 Provide cover plates for electrical outlets in following areas: 1.) laundry room 2.) in bdrms. #3 & #4 3.) main electrical panel,exterior, east side
09/04/2007 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Correction Required IFC 605.5 Extension cords shall not be a substitute for permanent wiring. 1.) main room, SE corner. 2.) laundry room.
09/04/2007 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Correction Required IFC 901.6.2 Provide smoke alarm testing records.
09/04/2007 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Correction Required IFC 907.2.10 Replace smoke alarm in pantry area and service smoke alarm in kitchen area.
09/04/2007 VIOL - MEANS OF EGRESS DRAMIREZ Correction Required IFC 1027.2 Service eegress windows to allow them to open more readily.
09/04/2007 VIOL - MEANS OF EGRESS DRAMIREZ Correction Required IFC 1027.3 Provide clear path, exit discharge, from emergency eegress windows, west side.