Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/29/2007

Applicant:

OLSEN AVENUE ASSOCIATES LLC

Description:

Full Inspection due to SIP forms not turned in w/in 30 days.

Outstanding Inspections

Case Number: T07FR01698
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
08/29/2007 INSP - FULL BCORRALE Continued Full inspection due to SIP form not turned in w/in 30 days.
08/29/2007 INSP - FULL BCORRALE Continued On 8-22-07, a fire prevention inspection was conducted at 1685 W. Valencia, #121. Please correct the following Tucson Fire Code violations. All references are from the 2006 International Fire Code, with modifications.
08/29/2007 VIOL - BUILDING SVCS & SYSTEMS BCORRALE Continued Rear exit blocked. 2006 IFC 1028.3- A means of egress shall be free from obstructions that would prevent its use. -Unblock door. (Door unblocked in my presence)
08/29/2007 VIOL - MEANS OF EGRESS BCORRALE Continued Electrical panel blocked. (rear stockroom) 2006 IFC 605.3- No storage of materials shall block working space of panels. -Unblock panels. (Unblocked in my presence)