Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01675
Case Description: INSPECTION
Total Completed Inspections - 8
End Date Description Inspector Results Comments
10/02/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2006 IFC 904.11.6.1 REPLACE MISSSING FILTERS IN HOOD.
10/02/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2006 IFC 901.6 SERVICE FIRE EXTINGUISHER BEHIND BAR IN PIT AREA. ALSO MOUNT EXTINGUISHER ON WALL. SERVICE AND TAG SPRINKLER SYSTEM SERVICE AND TAG K BOTTLE IN KITCHEN
10/02/2007 VIOL - COMPRESSED GASES MWAINWRI Approved 2006 IFC 3004.1 SECURE CO2 BOTTLES PROPERLY BY WOMENS BATHROOM. CHAIN BOTTLES BY SYRUP BOXES.
10/02/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1008.1.8.4 REMOVE SLIDE BOLTS ON BACK DOOR AND INSTALL A THUMB TURN LOCK TO SECURE DOOR.
10/02/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1027.3 REPAIR EXIT SIGN ON SW EXIT
10/02/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1027.5 REPAIR BROKEN EMERGENCY LIGHT ON NORTH EXIT
10/02/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1008.1.8.4 REMOVE DOUBLE KEYED LOCK AND REPLACE WITHA THUMB TURN LOCK.
12/20/2007 INSP - FULL MWAINWRI Approved