Case: T07FR01671
Case Details
Entered Date:
08/24/2007
Applicant:
INDUSTRIAL CHEMICAL OF ARIZONA INC
Description:
Full inspection done by Inspector John Bieg.
Outstanding Inspections
Case Number: T07FR01671
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2007 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2.1 Reduce storage height to 2 feet below the ceiling, in the stock rooms. |
| 08/24/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8 Remove the double keyed lock from the security door in the back warehouse. |
| 08/24/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.4 Remove the slide-bolt from the back warehouse door. |
| 08/24/2007 | VIOL - HAZARDOUS MATERIALS,GEN | JBURGE | Correction Required | TFC table 2703.1.1.1 Storage of a class 1 A flamable liquid shall not exceed 60 gallons when being stored in a flamable liquids cabinet. A re-inspection is scheduled for 9/5/07. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR01671
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/06/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 9/5/07. |