Case: T07FR01669
Case Details
Entered Date:
08/24/2007
Applicant:
OLYMPIC VIEW PROPERTIES INC
Description:
Full fire inspection done by Inspector John Bieg.
Outstanding Inspections
Case Number: T07FR01669
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/24/2007 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 505.1 #1.All exterior and interior apartment numbers shall comply with this code. #2.3710 and 3730 building numbers shall comply with this code. |
08/24/2007 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 506.1 Purchase a new fire departmant lock box and provide all necessary keys for access into the building, and alarm control panel. |
08/24/2007 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 510.1 Label the fire alarm control panel door so it will be readily identified. |
08/24/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.4 Remove the cube adapter located in the maintenance shop on the east wall, above the work bench. A re-inspection is scheduled for 9/5/07. |
08/24/2007 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | TFC 703.1 #1.Replace all broken and missing ceiling tiles. #2.Repair the damaged drywall in the maintenance shop. |
08/24/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 #1.Service and tag all hose cabinets. The hose cabinets have been appealed and removed allowed by Chief Uthe. #2.Service the stand pipe system. #3.Service and test the fire alarm system. #4.Service and tag all fire extinguishers that have not been serviced annually. NOTE:Correct all deficiencies and provide documentation of all work done. |
08/24/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8 The entrance/exit office door shall not have a double keyed lock. NOTE: Replace it with a thumb turn lock. |
08/24/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.3 The main entrance/exit at 3710 shall have this wording posted. |
08/24/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.3 All exit signs shall be illuminated. |
08/24/2007 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.5.3 Secure the compressed gas cylinder located in the office. NOTE: Use a chain or strap to secure the cylinder. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR01669
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/24/2007 | INSP - FULL | JBURGE | Approved | Please correct the following Tucson Fire Code violations: |