Description:

Full fire inspection done by Inspector John Bieg.

Outstanding Inspections

Case Number: T07FR01669
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
End Date Description Inspector Results Comments
08/24/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 505.1 #1.All exterior and interior apartment numbers shall comply with this code. #2.3710 and 3730 building numbers shall comply with this code.
08/24/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 506.1 Purchase a new fire departmant lock box and provide all necessary keys for access into the building, and alarm control panel.
08/24/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 510.1 Label the fire alarm control panel door so it will be readily identified.
08/24/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.4 Remove the cube adapter located in the maintenance shop on the east wall, above the work bench. A re-inspection is scheduled for 9/5/07.
08/24/2007 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1 #1.Replace all broken and missing ceiling tiles. #2.Repair the damaged drywall in the maintenance shop.
08/24/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 #1.Service and tag all hose cabinets. The hose cabinets have been appealed and removed allowed by Chief Uthe. #2.Service the stand pipe system. #3.Service and test the fire alarm system. #4.Service and tag all fire extinguishers that have not been serviced annually. NOTE:Correct all deficiencies and provide documentation of all work done.
08/24/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 The entrance/exit office door shall not have a double keyed lock. NOTE: Replace it with a thumb turn lock.
08/24/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.3 The main entrance/exit at 3710 shall have this wording posted.
08/24/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3 All exit signs shall be illuminated.
08/24/2007 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.5.3 Secure the compressed gas cylinder located in the office. NOTE: Use a chain or strap to secure the cylinder.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01669
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/24/2007 INSP - FULL JBURGE Approved Please correct the following Tucson Fire Code violations: