Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

08/21/2007

Applicant:

STAFF OF LIFE LLC

Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T07FR01619
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
08/23/2007 VIOL - FIRE SERVICE FEATURES MWAINWRI Violation 2006 IFC 504.2 POST A SIGN ON THE SW EXIT DOOR STATING THIS DOOR BLOCKED IN 3 INCH LETTERS.
08/23/2007 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Violation 2006 IFC 605.3 KEEP A 36 IN CLEARANCE AROUND ELECTRICAL PANEL.
08/23/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2006 IFC 901.6 HAVE SPRINKLER SYSTEM TESTED AND TAGGED. HAVE FIRE EXTINGUISHER SRVICED AND TAGGED.
08/23/2007 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1008.1.8.3 INSTALL A SIGN IN 1 INCH LETTERS ON FRONT DOOR STATING THIS DOOR TO REMAIN UNLOCKED DURING BUSINESS HOURS.
08/23/2007 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1027.3 REPAIR EXIT SIGN AT FRONT ENTRANCE.
08/23/2007 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1027.5 REPAIR EMERGENCY LIGHT ON WEST SIDE BY SPRINKLER RISER.