Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/20/2007

Applicant:

MENLO PARK SHOPPING CENTER COMPANY

Description:

Full fire inspection done by Inspector John Bieg.

Outstanding Inspections

Case Number: T07FR01613
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
08/20/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 505.1 The building address numbers shall comply with this code.
08/20/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 #1.Service and tag all portable fire extinguishers. #2.Service and tag the hood system.
08/20/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 Clean and remove all grease from the hood system and cooking equipment.
08/20/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3 #1.The northwest exit sign shall be fully illuminated. #2.The northeast exit sign shall be fully illuminated.
08/20/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 The exit sign located in the kitchen shall emergency back up power.
08/20/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.2 The exit door located in the kitchen shall not be obstructed at any time the building is occupied. A re-inspection is scheduled for 9/4/07.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01613
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/05/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 10/5/07.