Case: T07FR01613
Case Details
Entered Date:
08/20/2007
Applicant:
MENLO PARK SHOPPING CENTER COMPANY
Description:
Full fire inspection done by Inspector John Bieg.
Outstanding Inspections
Case Number: T07FR01613
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/20/2007 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 505.1 The building address numbers shall comply with this code. |
08/20/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 #1.Service and tag all portable fire extinguishers. #2.Service and tag the hood system. |
08/20/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.6.3 Clean and remove all grease from the hood system and cooking equipment. |
08/20/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.3 #1.The northwest exit sign shall be fully illuminated. #2.The northeast exit sign shall be fully illuminated. |
08/20/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5 The exit sign located in the kitchen shall emergency back up power. |
08/20/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1028.2 The exit door located in the kitchen shall not be obstructed at any time the building is occupied. A re-inspection is scheduled for 9/4/07. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR01613
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/05/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 10/5/07. |