Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

08/08/2007

Applicant:

PARKER AYSE

Description:

Full inspection per group home inspection.

Outstanding Inspections

Case Number: T07FR01511
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
08/08/2007 INSP - FULL DRAMIREZ Correction Required Assisted Living group home, licensed for 5, R-3
08/08/2007 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Correction Required IFC 605.4 Unapproved multiplug adaptors shall not be used. Outside freezer.(approved adaptors. power strip bar)
08/08/2007 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Correction Required IFC 605.5 Extension cords shall not be a substitute for permanent wiring. Outside freezer.
08/08/2007 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Correction Required IFC 901.6 Provide documentation of extinguisher annual inspection.
08/08/2007 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Correction Required IFC 901.6.2 Test records for smoke alarms shall be provided and shall be kept on site.
08/08/2007 VIOL - MEANS OF EGRESS DRAMIREZ Correction Required IFC 1008.18 Double- keyed deadbolt locks are not permitted.( Front door and front screen door and rear exit.) Replace with thumb-turn locks.