Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/07/2007

Applicant:

LOFT CINEMA INC

Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01507
Case Description: INSPECTION
Total Completed Inspections - 10
End Date Description Inspector Results Comments
09/28/2007 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Approved 2006 IFC 605.1 1) REPLACE MISSING COVER PLATE IN MAIN FILM ROOM OVER WORK BENCH. 2) REWIRE THE FLOURESCENT LIGHT IN UPPER FILM ROOM CNNOT USE SPEAKER WIRE. 3) NEED COVER PLATE ON OPEN JUNCTION BOX IN UPER FILM ROOM. 4) REMOVE THE 4 STRAND WIRE COMING OUT OF THE EMERGENCY LIGHT BOX. IT IS COILED ON THE FLOOR HAVING NO USE.
09/28/2007 VIOL - PRECAUTION AGAINST FIRE MWAINWRI Approved 2006. IFC 313.3 REMOVE THE GAS CAN AND POWERBLOWER FROM THE UPSTAIRS STORAGE ROOM.
09/28/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1027.13 INSTALL HANDRAIL ON ONE SIDE OF STAIR LEADING TO THE FILM ROOM. REMOVE THE CHAINS FROM THE 8 EXIT DOORS IN THE MAIN THEATER AND IN THE MAIN LOBBY.
09/28/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1003.6 REMOVE LADDER GOING INTO ATTIC IN THE UPSTAIRS THEATER. ALSO REMOVE THE WOOD BY THE EXIT DOOR. CLOSE CEILING HATCH WHEN REMOVING LADDER.
09/28/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1027.3 REPAIR THE 2 EXIT SIGNS UPSTAIRS.
09/28/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1027.5 INSTALL AN EMERGENCY LIGHT IN SW STAIRWAY.
09/28/2007 VIOL - FIRE RESIST.RATED CONST MWAINWRI Approved 2006 IFC 703.1 1) REPAIR HOLE IN CEILING IN UPER FILM ROOM. 2) REPAIR HOLE IN CEILING IN NW CORNER OF MAIN THEATER
09/28/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2006 IFC 901.6 1) HAVE ALL PORTABLE FIRE EXINGUISHERS SERVICED AND TAGGED. 2) HAVE ALL HOSE CABINETS INSPECTED AND TAGGED. 3) REPLACE MISSING ADJUSTABLE HOSE NOZZLE IN HOSE CABINET BEHIND MAIN THEATER SCREEN.
09/28/2007 VIOL - FIRE SERVICE FEATURES MWAINWRI Approved 2006 IFC 505.1 INSTALL ADDRESS NUMBERS ON BUILDING ACCORDING TO PIMA COUNTY ADDRESSING CODE.
09/28/2007 INSP - FULL MWAINWRI Approved