Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01489
Case Description: INSPECTION
Total Completed Inspections - 8
End Date Description Inspector Results Comments
11/07/2007 INSP - FULL MWAINWRI Approved
11/07/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2006 IFC 904.11.6.1 FIX EXHAUST HOOD SO THE FILTERS FIT TIGHT
11/07/2007 VIOL - FIRE RESIST.RATED CONST MWAINWRI Approved 2006 IFC 703.1 REPLACE CEILING TILE IN OFFICE AGAINST THE WALL.
11/07/2007 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Approved 2006 IFC 605.5 REMOVE EXTENSTION CORD IN OFFICE AND USE A POWER STRIP USE A POWER STRIP IN EAST SIDE VIDEO AREA
11/07/2007 VIOL - ADMINISTRATION MWAINWRI Approved 2006 IFC 110.4 INSTALL BLANK IN ELECTRICAL PANEL BY OFFICE INSTALL COVER PLATE IN CEILING IN RISER ROOM
11/07/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2006 IFC 901.6 HAVE ALL FIRE EXTINGUISHERS TAGGED AND SERVICED HAVE HOOD SYSTEM TESTED AND TAGGED.
11/07/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1027.5 REPAIR EMERGENCY LIGHT IN EAST STAIRWAY
11/07/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1027.3 REPAIR EXIT SIGN IN WEST STAIRWAY