Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/06/2007

Applicant:

LA FRONTERA CENTER INC

Description:

Group Home Inspection.

Outstanding Inspections

Case Number: T07FR01487
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
08/06/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required 23.TFC 603.1 & 316.2 Fuel fired appliances and house cleaning. Furnaces, dryer and hot water heaters are all heat sources and must be maintained and cleaned. 1.Clean the furnace closet to remove dust accumulation.
08/06/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required 23.TFC 603.1 & 316.2 Fuel fired appliances and house cleaning. Furnaces, dryer and hot water heaters are all heat sources and must be maintained and cleaned. 1.The furnace and water heater shall be properly vented and shall have combustible air supplied. A re-inspection is scheduled for 9-5-07.
08/06/2007 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required 18.TFC 703.1Must be repair w/ fire resistive materials Look behind washers and dryers, hot water heaters, heater closets. 1.The ceiling in bedroom # 4 shall be repaired.
08/06/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required 15. TFC 901.6.2 Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. 1.Smoke detector testing records shall be kept on site.
08/06/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required 16.TFC 907.3.1.8 Fire alarm systems Existing R4 must have a fire alarm system. Exception: interconnected, hardwired w/ battery backup smoke alarms Use # 15 code reference for records. 1.The fire alram test records shall be kept on site.
08/06/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required 25.TFC 1027.2 Maintenance of egress components Paths, doors, and ramps. Signs required in BHS The path is to a public way or a safe place. 1.The main entrance/exit shall not have two thumb turn locks.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01487
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/07/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 9/7/07.