Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/02/2007

Applicant:

KOGA RICHARD W & SONG C JT/RS

Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01468
Case Description: INSPECTION
Total Completed Inspections - 5
End Date Description Inspector Results Comments
10/17/2007 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Approved 2006 IFC 605.5 REMOVE EXTENSION CORD IN OFFICE PLUG VECTOR SYSTEM DIRECTLY INTO AN OUTLET (FLY TRAP)
10/17/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2006 IFC 904.11.5 NEED TO REPLACE THE DRY CHEM EXTINGUISHER IN TEPPAN ROOM AND BBQ ROOM WITH A CLASS K EXTINGUISHER
10/17/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2006 IFC 901.6 HAVE SPRINKLER HEADS CHECKED FOR PROPER PLACEMENT IN TEPPAN ROOM SERVICE AND TAG FIRE EXTINGUISHER IN KITCHEN EAST END
10/17/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2006 IFC 1027.3 EXIT SIGN IN TEPPAN ROOM NEEDS REPAIRED EXIT SIGNS IN SUSHI ROOM EXIT SIGN IN HALL BY OFFICE
10/17/2007 INSP - FULL MWAINWRI Approved