Case Details

Status:

COMPLETE

Type:

COMPLAINT (COMMERCIAL)
Address:

Entered Date:

08/02/2007

Applicant:

NATIONAL CHURCH RESIDENCES OF TUCSON AZ

Description:

No hydrants in service during construction phase, email came in from Mike Ward, there are only 2 hydrants planned for the property is this adequate for this type of occupancy?

Outstanding Inspections

Case Number: T07FR01460
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
08/02/2007 INSP - FULL ALOPEZ Correction Required email sent from Captain Mike Ward he states there are no hydrants in service on the properly during construction phase, also there are only 2 hydrants planned for the property is this adequate for this type of occupancy?

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01460
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/08/2007 COMPL - INITIAL INSPECTION DRAMIREZ Approved The area is in compliance with fire code requirements. All portions of this building are within 400 ft. of a hydrant and well within 600 ft., which a building is allowed to be if building is sprinklered. This building will be sprinklered. During the construction phase of this project, this building is provided with hydrants for protection from the surrounding area. A temporary breach has been made on the wall to the south of the construction site for better access and availability of those hydrants.