Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

08/02/2007

Applicant:

FERNANDEZ THERESA D OBREGON

Description:

Full inspection per Group Home inspection list.

Outstanding Inspections

Case Number: T07FR01458
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 12
End Date Description Inspector Results Comments
08/02/2007 INSP - FULL DRAMIREZ Correction Required Refered to building Safety. Behavioral Health group home, licensed for 10 occupants.
08/02/2007 VIOL - ADMINISTRATION DRAMIREZ Correction Required IFC 505.1 Address numbers on building not plainly visable.
08/02/2007 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Correction Required IFC 605.1 1.) Wiring in furnace room not wired to code. 2.) Wiring in laundry room not wired to code. 3.) cover plate under eve over driveway.
08/02/2007 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Correction Required IFC 603.1 Accumulation of lint and other combustible material behind washer / dryer.
08/02/2007 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Correction Required IFC 605.4 Unapproved multiplug adaptor in kitchen area next to refrigerator.
08/02/2007 VIOL - FIRE RESIST.RATED CONST DRAMIREZ Correction Required IFC 703.1 Repair damaged ceiling or walls in the following areas: 1.) replace cover for skuttle hole in hall closet. 2.) in hall closet. 3.) in furnace room. 4.) launrdy room.
08/02/2007 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Correction Required IFC 901.6 Portable fire extinguisher shall be mounted on wall and located in area of kitchen no closer then 10 ft. to stove.
08/02/2007 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Correction Required IFC 901.6 Extinguishers shall be inspected annually.
08/02/2007 VIOL - MEANS OF EGRESS DRAMIREZ Correction Required IFC 1008.18 Shall remove code operating locking devise from main exit and replace with approved locking devise.
08/02/2007 VIOL - MEANS OF EGRESS DRAMIREZ Correction Required IFC 1027.2 Window in bdrm #3 sticking, unable to open readily.
08/02/2007 VIOL - MEANS OF EGRESS DRAMIREZ Correction Required IFC 1027.3 / 1.) Tree branches obstructing exit from bdrm. #2 window. 2.) statue outside of bdrm. # 2 obstructing exit. 3.) Discontinue parking of vehicles in driveway directly in front of main exit.
08/02/2007 VIOL - MEANS OF EGRESS DRAMIREZ Correction Required IFC 1027.5 Bars on windows unable to open readily due to painting.