Case: T07FR01458
Case Details
Entered Date:
08/02/2007
Applicant:
FERNANDEZ THERESA D OBREGON
Description:
Full inspection per Group Home inspection list.
Outstanding Inspections
Case Number: T07FR01458
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 12
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2007 | INSP - FULL | DRAMIREZ | Correction Required | Refered to building Safety. Behavioral Health group home, licensed for 10 occupants. |
| 08/02/2007 | VIOL - ADMINISTRATION | DRAMIREZ | Correction Required | IFC 505.1 Address numbers on building not plainly visable. |
| 08/02/2007 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Correction Required | IFC 605.1 1.) Wiring in furnace room not wired to code. 2.) Wiring in laundry room not wired to code. 3.) cover plate under eve over driveway. |
| 08/02/2007 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Correction Required | IFC 603.1 Accumulation of lint and other combustible material behind washer / dryer. |
| 08/02/2007 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Correction Required | IFC 605.4 Unapproved multiplug adaptor in kitchen area next to refrigerator. |
| 08/02/2007 | VIOL - FIRE RESIST.RATED CONST | DRAMIREZ | Correction Required | IFC 703.1 Repair damaged ceiling or walls in the following areas: 1.) replace cover for skuttle hole in hall closet. 2.) in hall closet. 3.) in furnace room. 4.) launrdy room. |
| 08/02/2007 | VIOL - FIRE PROTECTION SYSTEMS | DRAMIREZ | Correction Required | IFC 901.6 Portable fire extinguisher shall be mounted on wall and located in area of kitchen no closer then 10 ft. to stove. |
| 08/02/2007 | VIOL - FIRE PROTECTION SYSTEMS | DRAMIREZ | Correction Required | IFC 901.6 Extinguishers shall be inspected annually. |
| 08/02/2007 | VIOL - MEANS OF EGRESS | DRAMIREZ | Correction Required | IFC 1008.18 Shall remove code operating locking devise from main exit and replace with approved locking devise. |
| 08/02/2007 | VIOL - MEANS OF EGRESS | DRAMIREZ | Correction Required | IFC 1027.2 Window in bdrm #3 sticking, unable to open readily. |
| 08/02/2007 | VIOL - MEANS OF EGRESS | DRAMIREZ | Correction Required | IFC 1027.3 / 1.) Tree branches obstructing exit from bdrm. #2 window. 2.) statue outside of bdrm. # 2 obstructing exit. 3.) Discontinue parking of vehicles in driveway directly in front of main exit. |
| 08/02/2007 | VIOL - MEANS OF EGRESS | DRAMIREZ | Correction Required | IFC 1027.5 Bars on windows unable to open readily due to painting. |