Case: T07FR01454
Case Details
Entered Date:
08/01/2007
Applicant:
MONTEREY WATER CO
Description:
Full Inspection
Outstanding Inspections
Case Number: T07FR01454
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/01/2007 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Storage shall be 18 inches below sprinkler heads. |
08/01/2007 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8 Lock at south exit door shall not require special knowledge. |
08/01/2007 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.3 Exit sign at east exit. |
08/01/2007 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.3 Exit sign at NW exit O/S |
08/01/2007 | VIOL - HAZARDOUS MATERIALS,GEN | TKNAPP | Correction Required | 2703.5.1 Containers shall be labeled. |
08/01/2007 | VIOL - FLAMMABLE LIQUIDS | TKNAPP | Correction Required | 3404.3.3.3 Flammible liquids located near exit. |
08/01/2007 | VIOL - FLAMMABLE LIQUIDS | TKNAPP | Correction Required | 3404.3.4.4 Quantities of flammable liquids in excess of 10 gallons. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR01454
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/05/2007 | INSP - FULL | TKNAPP | Approved |