Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

07/26/2007

Applicant:

USTARIZ GERMAN

Description:

Full fire inspection done by Inspector John Bieg on 7/26/07. "S-2"

Outstanding Inspections

Case Number: T07FR01401
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
07/26/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 #1.Service and tag the automatic sprinkler system. #2.Service and tag all portable fire extinguishers. #3.The fire department connections shall have an inlet cover.
07/26/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.2 #1.The west exit door in the warehouse shall not be obstructed. #2.The north exit door located by UL 1 shall not be obstructed. #3.The east exit door located in the warehouse shall not be obstructed. A re-inspection is scheduled for 8/9/07.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01401
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/27/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 9-17-07.