Description:

Full fire inspection done by Inspector John Bieg on 7/25/07. "B" Restaurant.

Outstanding Inspections

Case Number: T07FR01398
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
07/26/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5 #1.Remove the extension cord located below the register. #2.Remove the extension cord used to power the frige. NOTE:Replace them with fused power strips.
07/26/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 Clean and remove the grease accumulation built up on the cooking equipment and hood system.
07/26/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 Remove the double keyed lock from the exit door in the kitchen. {Replace it with a thumb turn lock.}
07/26/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.5 Remove the thumb turn lock from the door knob. A re-inspection is scheduled for 8/8/07.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01398
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/18/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 8/17/07.