Case: T07FR01378
Case Details
Entered Date:
07/25/2007
Applicant:
LA LUNA LLC
Description:
Full Fire Inspection
Outstanding Inspections
Case Number: T07FR01378
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/27/2007 | VIOL - ADMINISTRATION | NSPRENGE | Violation | IFC 104.3 The fire code official shall have access to the building to donduct a fire inspection. Unlock the South door in the bathroom hallway. |
07/27/2007 | VIOL - PRECAUTION AGAINST FIRE | NSPRENGE | Violation | IFC 315.2.1 Storage shall be maintained 2 feet or more below the ceiling in an unsprinklered building. Maintain 2 feet of clearance in storage area on the racks. |
07/27/2007 | VIOL - BUILDING SVCS & SYSTEMS | NSPRENGE | Violation | IFC 605.5 Approved covers shall be provided for all electrical outelet boxes and switch boxes. Place covers on open circuits in both electric panels on the S Kitchen wall near rack storage (3 total). |
07/27/2007 | VIOL - FIRE PROTECTION SYSTEMS | NSPRENGE | Violation | IFC 904.11.6.4 Certifcate of inspection for automatic fire extinguishing systems for commercial cooking equipment shall be fowarded to the fire inspector upon completion of inspection ( every 6 monthes ). Ecquire paperwork for last inspection and foward it or fax it to Fire Prevention. |
07/27/2007 | VIOL - MEANS OF EGRESS | NSPRENGE | Violation | IFC 1028.3 Exits shall be free from obstructions. Remove boxes blocking S kitchen exit. |
07/27/2007 | VIOL - COMPRESSED GASES | NSPRENGE | Violation | IFC 3003.5 Compressed gas cylinders shall be secured against accidental dislodgement, by securing to a fixed object with chain or restraint. Secure your CO2 bottle (cylinder) in kitchen store room. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR01378
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/19/2007 | INSP - FULL | JDAVIS | Approved | conducted re insp. Sept. 6,10 2007, All items abated |