Case: T07FR01375
Case Details
Entered Date:
07/25/2007
Applicant:
JEWELL STEVE & MARY TR II
Description:
Full fire inspection done by Inspector John Bieg on 7/23/07. "S-1".
Outstanding Inspections
Case Number: T07FR01375
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/25/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.5 Remove all extension cords used for permanent wiring located in the shop. {Replace them with fused power strips.} |
| 07/25/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 Service the solvent dip tank used for cleaning auto parts. {Show documentation of current service and testing.} |
| 07/25/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.5 Remove the locking door knob from the egress door in the office. |
| 07/25/2007 | VIOL - HAZARDOUS MATERIALS,GEN | JBURGE | Correction Required | TFC 2703.3 Cleanup the spilled waste oil from the concrete pad and soil, by the outside tank. |
| 07/25/2007 | VIOL - HAZARDOUS MATERIALS,GEN | JBURGE | Correction Required | TFC 2703.5.1 All individual containers that are not labeled shall be labeled, to identify the contents of the container. |
| 07/25/2007 | VIOL - HAZARDOUS MATERIALS,GEN | JBURGE | Correction Required | TFC 2703.7.1 The shop shall have " no smoking" signs posted inside. |
| 07/25/2007 | VIOL - FLAMMABLE LIQUIDS | JBURGE | Correction Required | TFC 3404.3.2 Flamable and combustible liquids being used shall be stored in an approved liquid storage cabinet. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR01375
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/31/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected. |