Description:

Full fire inspection done by Inspector John Bieg on 7/17/07. "A-2"/Restaurant.

Outstanding Inspections

Case Number: T07FR01341
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
07/18/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 508.5.4 The dish washer unit shall not obstruct access to the manual pull station for the kitchen hood system. A re-inspection is scheduled for 7/31/07.
07/18/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5 Remove the extension cord used to power the dish washer.
07/18/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 #1.Submit plans for approval of the addition of hood system nozzles, for proper cooking equipment coverage. #2.Service and tag the kitchen hood system. #3.Service, tag and recharge the class K fire extinguisher.
07/18/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.5 The hot dog stand shall have a fire extinguisher located within 30 feet when being used.
07/18/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 Provide documentation of hood system cleanings.
07/18/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 Remove the padlock and hardware from the exterior side of the south exit door. {Use a thumb turn lock on the inside.}
07/18/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3 #1.The south exit sign shall be illuminated. #2.The northwest exit sign shall be illuminated.
07/18/2007 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.5.3 Secure the compressed gas cylinders located in the kitchen. {Use a chain or other approved restraint device.}

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01341
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/24/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 9-24-07.