Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

07/16/2007

Applicant:

SOLAR HOLDINGS LLC

Description:

Full fire inspection done by Inspector John Bieg on 7/16/07. "A-2" /Restaurant.

Outstanding Inspections

Case Number: T07FR01329
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
07/16/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2 Combustible materisals shall not be stored next to the deep fat fryers located in the kitchen. A re-inspection is scheduled for 7/29/07.
07/16/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 506.1 Purchase a fire department lock.
07/16/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 508.5.4 There shall be no storage around the sprinkler riser pipe and fire department connections.
07/16/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 510.1 Post signs indicating the location of the fire department inlet connections.
07/16/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 #1. Service and tag the class K fire extinguisher located on the east side of the kitchen. {Missing service tag.} #2. Submit plans for approval of the addition of nozzles, for proper coverage of the commercial kitchen equipment. {Burners are not protected by the hood system.} #3. The hood system nozzles used for the fryer's and grill shall be placed properly to cover the cooking equipment. #4. The FDC inlet covers are missing and shall be replaced.
07/16/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.4 Remove the surface bolt from the exit gate in the patio.
07/16/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 The west exit sign shall have emergency back-up power.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01329
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/24/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 9-24-07.