Case: T07FR01329
Case Details
Entered Date:
07/16/2007
Applicant:
SOLAR HOLDINGS LLC
Description:
Full fire inspection done by Inspector John Bieg on 7/16/07. "A-2" /Restaurant.
Outstanding Inspections
Case Number: T07FR01329
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/16/2007 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2 Combustible materisals shall not be stored next to the deep fat fryers located in the kitchen. A re-inspection is scheduled for 7/29/07. |
07/16/2007 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 506.1 Purchase a fire department lock. |
07/16/2007 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 508.5.4 There shall be no storage around the sprinkler riser pipe and fire department connections. |
07/16/2007 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 510.1 Post signs indicating the location of the fire department inlet connections. |
07/16/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 #1. Service and tag the class K fire extinguisher located on the east side of the kitchen. {Missing service tag.} #2. Submit plans for approval of the addition of nozzles, for proper coverage of the commercial kitchen equipment. {Burners are not protected by the hood system.} #3. The hood system nozzles used for the fryer's and grill shall be placed properly to cover the cooking equipment. #4. The FDC inlet covers are missing and shall be replaced. |
07/16/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.4 Remove the surface bolt from the exit gate in the patio. |
07/16/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5 The west exit sign shall have emergency back-up power. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR01329
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/24/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 9-24-07. |