Description:

Full fire inspection done by Inspector John Bieg on 7/9/07. "M"

Outstanding Inspections

Case Number: T07FR01305
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
07/11/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2 Storage located in the back room and the offices shall be orderly.
07/11/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.1 The sprinkler heads located under the overhang on the east wall shall comply with this code.
07/11/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 505.1 Comply with this code.
07/11/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3 Remove the storage from blocking the electrical service equipment located in the back room.
07/11/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Service, tag and mount the portable fire extinguisher located in the back room. A re-inspection is scheduled for 7/23/07.
07/11/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.1 #1. The southeast exit doors shall have an internally or externally illuminated exit sign posted above the doors. #2. The southwest exit doors shall have an internally or externally illuminated exit sign posted above the doors.
07/11/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.5 #1. Repair the emergency lighting unit located above the rice. #2. Repair the emergency lighting unit located on the ceiling near the southeast exit doors.
07/11/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.2 The southeast exit door shall not be blocked.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01305
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/23/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 7/23/07. Inspector John Bieg.