Case: T07FR01274
Case Details
Entered Date:
07/05/2007
Applicant:
DANVILLE SERVICES CORP
Description:
Full inspection per Group Home check list.
Outstanding Inspections
Case Number: T07FR01274
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 8
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/05/2007 | INSP - FULL | DRAMIREZ | Correction Required | DDD Child Group Home licensed for 5 occupants. |
| 07/06/2007 | VIOL - ADMINISTRATION | DRAMIREZ | Correction Required | IFC 102.3 Shall provide and shall post C of O. |
| 07/06/2007 | VIOL - EMERGENCY PLAN/PREPARE | DRAMIREZ | Correction Required | IFC 405.5 Shall provide fire drill documentation. |
| 07/06/2007 | VIOL - FIRE SERVICE FEATURES | DRAMIREZ | Correction Required | IFC 605.4 Multi-plug adaptors (power strip bars) shall be connected directly into the power source. (no piggy- backing) |
| 07/06/2007 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Correction Required | IFC 605.1 1.) Romex wiring supplying flood lights located to the front of the building is being damaged by weather. The wire currently in place shall be replaced with new wire and protected in conduit. 2.) Kitchen sink shall be provided with GFCI. |
| 07/06/2007 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Correction Required | IFC 605.7 Secure exhust fan in bathroom. |
| 07/06/2007 | VIOL - FIRE PROTECTION SYSTEMS | DRAMIREZ | Correction Required | IFC 901.6.2 Shall provide documentation of smoke alarm inspections. |
| 07/06/2007 | VIOL - MEANS OF EGRESS | DRAMIREZ | Correction Required | IFC 1027.2 Window in NE bedroom shall be readily openable. |