Description:
Full inspection per GH check list.
Outstanding Inspections
Case Number: T07FR01254
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 6
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/03/2007 | INSP - FULL | DRAMIREZ | Correction Required | DES juvenile group home licensed for 8 |
| 07/03/2007 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Correction Required | IFC 605.1 Electrical. 1.) lable electrical panel in hall closet. 2.) provide blanks for exterior elctrical panel. |
| 07/03/2007 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Correction Required | IFC 605.4 Remove multi-plug adaptor from behind kitchen refrigerator. |
| 07/03/2007 | VIOL - FIRE PROTECTION SYSTEMS | DRAMIREZ | Correction Required | IFC 907.2.10 Relocate smoke alarm on hallway, from wall to ceiling. |
| 07/03/2007 | VIOL - MEANS OF EGRESS | DRAMIREZ | Correction Required | IFC 1008.1.8 Double keyed locks on secondary exits in bedroom doors shall be removed. ( ruling pending on review of existing approved plans). |
| 07/03/2007 | VIOL - MEANS OF EGRESS | DRAMIREZ | Correction Required | IFC 1027.2 Exits not readily accessable. ( Refer to violation of IFC 1008.1.8 ) |