Case: T07FR01235
Case Details
Entered Date:
07/02/2007
Applicant:
LONG ROBERT R 1/2 & LONG DALE H & LONG
Description:
Full fire inspection done by Inspector John Bieg on 6/29/07. A-2/Restaurant.
Outstanding Inspections
Case Number: T07FR01235
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/2007 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 505.1 Address numbers. 1. Comply with this code. |
| 07/02/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 #1. Service and tag the hood system. #2. Service and tag all portable fire extinguishers. |
| 07/02/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.6.3 Clean all hood systems. Provide documentation of cleanings. |
| 07/02/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1004.3 The occupant load shall be posted and meet the specified requirements. A re-inspection is scheduled for 7/13/07. |
| 07/02/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.3 The northeast exit door shall comply with this code. |
| 07/02/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1026.3 The exit sign located in the kitchen shall be illuminated. |
| 07/02/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.6 Remove the double keyed deadbolt from the southeast exit door. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR01235
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 8/1/07. |