Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

06/29/2007

Applicant:

GOWDY BARBARA T TR

Description:

Full fire inspection done by Inspector John Bieg on 6/29/07.

Outstanding Inspections

Case Number: T07FR01229
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
06/29/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 505.1 Comply with this code.
06/29/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 508.5.4 #1. Remove storage from obstructing the sprinkler system riser pipe. #2. Remove the tree branches from obstructing the fire department connections located on the northeast side of the building.
06/29/2007 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1 Repair the holes in the wall located in the copper room. NOTE: The addition of the counter sales area and the northwest office was done without permits. This issue has been refered to DNR. A re-inspection is scheduled for 7/13/07.
06/29/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 #1.Service and tag the automatic sprinkler system. #2. Service and tag all fire extinguishers. #3. Service and tag the fire hose cabinet.
06/29/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.1 The west exit door located in the warehouse shall have an approved exit sign.
06/29/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.3 Thew exit sign located above the east exit door in the warehouse shall be illuminated.
06/29/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.4 The exit sign located in counter sales shall have emergency back-up power. NOTE: Test all emergency lighting in the warehouse.
06/29/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.2 Remove all storage from blocking the exit door located on the east side of the warehouse.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01229
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/01/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 8/1/07.