Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T07FR01229
Case Details
Entered Date:
06/29/2007
Applicant:
GOWDY BARBARA T TR
Description:
Full fire inspection done by Inspector John Bieg on 6/29/07.
Outstanding Inspections
Case Number: T07FR01229
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/29/2007 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 505.1 Comply with this code. |
06/29/2007 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 508.5.4 #1. Remove storage from obstructing the sprinkler system riser pipe. #2. Remove the tree branches from obstructing the fire department connections located on the northeast side of the building. |
06/29/2007 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | TFC 703.1 Repair the holes in the wall located in the copper room. NOTE: The addition of the counter sales area and the northwest office was done without permits. This issue has been refered to DNR. A re-inspection is scheduled for 7/13/07. |
06/29/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 #1.Service and tag the automatic sprinkler system. #2. Service and tag all fire extinguishers. #3. Service and tag the fire hose cabinet. |
06/29/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1011.1 The west exit door located in the warehouse shall have an approved exit sign. |
06/29/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1026.3 Thew exit sign located above the east exit door in the warehouse shall be illuminated. |
06/29/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1026.4 The exit sign located in counter sales shall have emergency back-up power. NOTE: Test all emergency lighting in the warehouse. |
06/29/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.2 Remove all storage from blocking the exit door located on the east side of the warehouse. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR01229
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/01/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 8/1/07. |