Case: T07FR01146
Case Details
Entered Date:
06/18/2007
Applicant:
EICH PEGGY
Description:
Full Inspection
Outstanding Inspections
Case Number: T07FR01146
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/18/2007 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 Extinguisher at kitchen near sink shall be inspected. |
| 06/18/2007 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 Extinguisher at north end of hood system shall be inspected. |
| 06/18/2007 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.6.4 Hood system shall be inspected every 6 months. |
| 06/18/2007 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1003.4 The floor in the kitchen shall be maintained slip resistant. |
| 06/18/2007 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 Exit sign at dining area east exit. |
| 06/18/2007 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 Exit sign at west dining area exit. |
| 06/18/2007 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.5 Emergency lights at dining area west exit. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR01146
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2007 | INSP - FULL | TKNAPP | Approved |