Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

06/11/2007

Applicant:

SYSTEM CAPITAL REAL PROPERTY CORP

Description:

Full Inspection

Outstanding Inspections

Case Number: T07FR01113
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
06/11/2007 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 Electrical panels in SW equipment room shall be accessible.
06/11/2007 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1 Missing ceiling tile in equipment room shall be replaced.
06/11/2007 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 904.11.6.1 Filters shall be in place when operating hood system.
06/11/2007 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 906.7 The portable fire extinguisher at the rear exit shall be mounted on a hanger.
06/11/2007 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8.4 Surface bolt lock at rear exit shall be removed.
06/11/2007 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 Trash can shall not be allowed to obstruct exit.
06/11/2007 VIOL - COMPRESSED GASES TKNAPP Correction Required 3003.3 Compressed gas cylinder in equipment room shall be secured.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01113
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/25/2007 INSP - FULL TKNAPP Approved