Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

06/08/2007

Applicant:

CAJUN OPERATING COMPANY

Description:

Full Fire Inspection

Outstanding Inspections

Case Number: T07FR01109
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
06/08/2007 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation 1. IFC 605.6 Open junction boxes or wiring splices are prohibited. Replace emergency lighting on W wall and cover wires.
06/08/2007 VIOL - MEANS OF EGRESS NSPRENGE Violation 2. IFC 1006.3 Power for emergency lighting shall be provided by premises electrical supply. There shall be back up power by batteries. Replace bulbs in emergency lighing at rear kitchen exit.
06/08/2007 VIOL - MEANS OF EGRESS NSPRENGE Violation 4. IFC 1011.5.1 Every exit sign shall have plainly legible letters - 6 inches high. Replace broken exit sign over the rear kitchen exit.
06/08/2007 VIOL - MEANS OF EGRESS NSPRENGE Violation IFC 1011.2 Exit signs shall be illuminated at all times. Replace back up batteries for two exit signs in the lobby.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01109
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/12/2007 INSP - REINSPECTION NSPRENGE Approved ON SECOND REINSPECTION, BUSINESS IN COMPLIANCE ALL VIOLATIONS/HAZARDS EBATED.