Case Number: T07FR01108
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
06/08/2007 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 906.7 Extinguisher on floor at office area shall be mounted.
06/08/2007 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.5 The emergency light located in the dining room at the northwest corner shall be repaired.
06/08/2007 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.5 The emergency light located in the east drive thru window shall be repaired.
06/08/2007 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.6 Where panic hardware is installed whether required or not panic hardware shall be the only locking device on the door. The double keyed locks on the 3 dining room doors shall be removed.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01108
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/11/2007 INSP - FULL TKNAPP Approved