Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

06/05/2007

Applicant:

TUCSON ST MARY'S PLAZA LLC

Description:

Full fire inspection done by inspector John Bieg on 6/4/07. "B" / Restaurant.

Outstanding Inspections

Case Number: T07FR01077
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
06/05/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 505.1 Comply with this code.
06/05/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6 The electrical outlet located in the office shall have an approved cover.
06/05/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 Clean and remove all grease accumulation from the hood system and cooking equipment. { Provide documentation of such cleaning.} A re-inspection is scheduled for 6/26/07.
06/05/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.3 #1. The east exit sign shall be illuminated. #2. The west exit sign shall be illuminated. #3. The exit sign located in the kitchen shall be illuminated.
06/05/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.5 Repair the emergency lighting unit located in the kitchen.
06/05/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.6 Remove the thumb turn lock from the exit door located in the kitchen.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01077
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/17/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 8/16/07.