Case: T07FR01071
Case Details
Entered Date:
06/04/2007
Applicant:
N/A
Description:
Full fire inspection done by Inspector John Bieg on 6/4/07. "A-2" / Restaurant.
Outstanding Inspections
Case Number: T07FR01071
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/04/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3 Remove storage from blocking the electrical service panel located in the kitchen by the exit door. A re-inspection is scheduled for 6/25/07. |
| 06/04/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 #1. Submit plans for the addition of hood system nozzles, for proper coverage of the cooking equipment. #2. Service and tag the hood system. {Repair the pull station.} |
| 06/04/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.6.3 Clean the hood system and maintain records of cleanings. {Remove all grease accumulation.} |
| 06/04/2007 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.3.3 Secure the compressed gas cylinders located in the kitchen. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR01071
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 7/6/07. Inspector John Bieg. |