Status:

COMPLETE

Type:

INSPECTION

Entered Date:

06/04/2007

Applicant:

N/A

Description:

Full fire inspection done by Inspector John Bieg on 6/4/07. "A-2" / Restaurant.

Outstanding Inspections

Case Number: T07FR01071
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
06/04/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3 Remove storage from blocking the electrical service panel located in the kitchen by the exit door. A re-inspection is scheduled for 6/25/07.
06/04/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 #1. Submit plans for the addition of hood system nozzles, for proper coverage of the cooking equipment. #2. Service and tag the hood system. {Repair the pull station.}
06/04/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 Clean the hood system and maintain records of cleanings. {Remove all grease accumulation.}
06/04/2007 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.3.3 Secure the compressed gas cylinders located in the kitchen.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01071
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/09/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 7/6/07. Inspector John Bieg.