Description:

Full fire inspection done by Inspector John Bieg on 6/1/07. "B" / Restaurant.

Outstanding Inspections

Case Number: T07FR01064
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
06/01/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6 The electrical outlet located in the kitchen on the north wall, shall have an approved cover. A re-inspection is scheduled for 6/25/07.
06/01/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 #1. Service and tag the hood system. #2. Service and tag the class K portable fire extinguisher.
06/01/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 Clean the hood system and remove all grease from behind the cooking equipment. Show documentation of cleaning activities.
06/01/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.7 Mount the class K portable fire extinguisher.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01064
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/01/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 8/1/07.