Case: T07FR01064
Case Details
Entered Date:
06/01/2007
Applicant:
VAM REALTY LIMITED PARTNERSHIP
Description:
Full fire inspection done by Inspector John Bieg on 6/1/07. "B" / Restaurant.
Outstanding Inspections
Case Number: T07FR01064
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/01/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.6 The electrical outlet located in the kitchen on the north wall, shall have an approved cover. A re-inspection is scheduled for 6/25/07. |
| 06/01/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 #1. Service and tag the hood system. #2. Service and tag the class K portable fire extinguisher. |
| 06/01/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.6.3 Clean the hood system and remove all grease from behind the cooking equipment. Show documentation of cleaning activities. |
| 06/01/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 906.7 Mount the class K portable fire extinguisher. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR01064
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 8/1/07. |