Case: T07FR01059
Case Details
Entered Date:
05/31/2007
Applicant:
VAM REALTY LIMITED PARTNERSHIP
Description:
Full fire inspection done by Inspector John Bieg on 5/31/07. "A-2" / Restaurant.
Outstanding Inspections
Case Number: T07FR01059
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/31/2007 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2 Remove storage from around the water heater located in the kitchen. |
| 05/31/2007 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 505.1 Comply with this code. A re-inspection is scheduled for 6/8/07. |
| 05/31/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1011.2 All exit signs shall be fully illuminated. |
| 05/31/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1026.5 #1. Repair all emergency lighting located in the meeting room. #2. Repair all emergency lighting located in the lobby. |
| 05/31/2007 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.3.3 Secure the compressed gas cylinders located in the kitchen with a chain or other approved device. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR01059
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 8/2/07. |