Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

05/31/2007

Applicant:

LEE FAMILY PROPERTY MANAGEMENT LLP

Description:

Full fire inspection done by Inspector John Bieg on 5/31/07. "B"/Restaurant.

Outstanding Inspections

Case Number: T07FR01055
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
05/31/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 Clean the hood system. Show documentation of the cleaning.
05/31/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 #1. Remove the manually operated flush bolt from the exit door located in the kitchen. #2. Remove the locking bar hardware from the exit door located in the kitchen.
05/31/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.2 #1. The exit sign located in the dinning area shall be illuminated. #2. The exit sign located in the kitchen shall be illuminated.
05/31/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFc 1026.5 #1. Repair the emergency lighting unit located in the dinning area on the wall. #2. Repair the emergency lighting unit located in the kitchen above the pull station for the hood system.
05/31/2007 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.3.3 Secure the compressed gas cylinder used for the soda machine. Use a chain or other approved securing device. A re-inspection is scheduled for 6/8/07.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01055
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/30/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 7/30/07.