Full fire inspection done by Inspector John Bieg on 5/25/07. "B" / Restaurant.

Outstanding Inspections

Case Number: T07FR01015
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
05/29/2007 VIOL - ADMINISTRATION JBURGE Correction Required TFC 107.1 #1. The exit sign located in the kitchen shall be repaired and shall be fully illuminated. #2. The emergency lighting unit located by the exit door shall be repaired. A re-inspection is scheduled for 6/8/07.
05/29/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 505.1 Comply with this code.
05/29/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 #1. Service and tag the class K portable fire extinguisher. #2. Service and tag the hood systems.
05/29/2007 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.3.3 Secure the carbon dioxide cylinders with a chain. { the tanks are located by the exit door.}

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01015
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/09/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 8/8/07.