Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T07FR01015
Case Details
Entered Date:
05/29/2007
Applicant:
FUTER RUDOLPH E
Description:
Full fire inspection done by Inspector John Bieg on 5/25/07. "B" / Restaurant.
Outstanding Inspections
Case Number: T07FR01015
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/29/2007 | VIOL - ADMINISTRATION | JBURGE | Correction Required | TFC 107.1 #1. The exit sign located in the kitchen shall be repaired and shall be fully illuminated. #2. The emergency lighting unit located by the exit door shall be repaired. A re-inspection is scheduled for 6/8/07. |
05/29/2007 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 505.1 Comply with this code. |
05/29/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 #1. Service and tag the class K portable fire extinguisher. #2. Service and tag the hood systems. |
05/29/2007 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.3.3 Secure the carbon dioxide cylinders with a chain. { the tanks are located by the exit door.} |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR01015
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/09/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 8/8/07. |