Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

05/25/2007

Applicant:

MENLO PARK SHOPPING CENTER COMPANY

Description:

Full fire inspection was done by Inspector John Bieg on 5/25/07. "A-2" / Restaurant.

Outstanding Inspections

Case Number: T07FR01009
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
05/25/2007 VIOL - ADMINISTRATION JBURGE Correction Required TFC 107.1 Repair the exit sign located in the kitchen above the south exit door.
05/25/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.4.2 Fused plug strips shall not be pluged into another plug strip. { In the office on the east wall. } A re-inspection is schedeuled for 6/8/07.
05/25/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Repair the red taged hood system.
05/25/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 Clean all hood systems and maintain records of cleanings on the premises.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR01009
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/12/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 6/8/07. Inspector John Bieg.