Case: T07FR01009
Case Details
Entered Date:
05/25/2007
Applicant:
MENLO PARK SHOPPING CENTER COMPANY
Description:
Full fire inspection was done by Inspector John Bieg on 5/25/07. "A-2" / Restaurant.
Outstanding Inspections
Case Number: T07FR01009
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/25/2007 | VIOL - ADMINISTRATION | JBURGE | Correction Required | TFC 107.1 Repair the exit sign located in the kitchen above the south exit door. |
05/25/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.4.2 Fused plug strips shall not be pluged into another plug strip. { In the office on the east wall. } A re-inspection is schedeuled for 6/8/07. |
05/25/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 Repair the red taged hood system. |
05/25/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.6.3 Clean all hood systems and maintain records of cleanings on the premises. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR01009
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/12/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 6/8/07. Inspector John Bieg. |