Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

05/22/2007

Applicant:

FIESTA LANES LLC

Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00995
Case Description: INSPECTION
Total Completed Inspections - 15
End Date Description Inspector Results Comments
06/19/2007 VIOL - FIRE RESIST.RATED CONST MWAINWRI Approved
06/19/2007 VIOL - FIRE RESIST.RATED CONST MWAINWRI Approved 2003 IFC 703.1 REPAIR HOLES IN CEILING IN RISER ROOM.
06/19/2007 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Approved
06/19/2007 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Approved 2003 IFC 605.1 INSTALL BLANKS IN ELECTRICAL PANEL IN PIT AREA.
06/19/2007 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Approved 2003 IFC 605.3.1 1) MARK DOOR IN OFFICE GOING TO RISER/ELECTRICAL ROOM WITH A SIGN ON DOOR STATING ELECTRICAL ROOM AND RISER ROOM. 2) MARK DOO ON OUTSIDE DOOR OF RISER/ELECTRICAL ROOM WITH SIGN STATING ELECTRICAL ROOM AND RISER ROOM.
06/19/2007 VIOL - BUILDING SVCS & SYSTEMS MWAINWRI Approved 2003 IFC 605.3 1) KEEP 36" CLEARANCE AROUND ELECTRICAL PANEL 2) KEEP 36" CLEARANCE AROUND TRANSFORMER.
06/19/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved
06/19/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2003 IFC 901.6 FIRE EXTINGUISHERS IN PIT AREA NEED TESTING.
06/19/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2003 IFC 901.6 HAVE SPRINKLER SYSTEM TESTED, INSPECTED AND TAGGED.
06/19/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2003 904.11.5 NEED TO INSTALL A K BOTTLE EXTINGUISHER IN KITCHEN.
06/19/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved
06/19/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2003 IFC 1026.5 REPAIR THE 3 EMERGENCY LIGHTS IN PIT AREA.
06/19/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2003 IFC 1008.1.8.4 REMOVE SLIDE BOLT FROM EAST AND WEST EMERGENCY DOORS IN PIT AREA.
06/19/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2003 IFC 1926.5 REPAIR EMERGENCY LIGHT IN PLAY ROOM
06/19/2007 INSP - FULL MWAINWRI Approved