Case: T07FR00974
Case Details
Entered Date:
05/18/2007
Applicant:
EL CAMPO PROPERTIES LLLP
Description:
Full Fire Inspection
Outstanding Inspections
Case Number: T07FR00974
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/18/2007 | INSP - FULL | NSPRENGE | Correction Required | |
| 05/18/2007 | VIOL - FIRE RESIST.RATED CONST | NSPRENGE | Violation | IFC 703.1 The required fire resistance rating of fire resistive rated construction ashall be maintained. Repair the opening in the ceiling of the shop over restroom. |
| 05/18/2007 | VIOL - FIRE PROTECTION SYSTEMS | NSPRENGE | Violation | IFC 906.2 Fire extinguishers shall be maintained. Have your fire extinguishers serviced annually and tagged for approval. |
| 05/18/2007 | VIOL - FIRE PROTECTION SYSTEMS | NSPRENGE | Violation | IFC 906.7 Hand held portable fire extinguishers shall be installed on hangers or brackets supplied. Mount any fire extingushers that are not already on brackets. ( 3 pressurized water extinguishers). |
| 05/18/2007 | VIOL - MEANS OF EGRESS | NSPRENGE | Violation | IFC 1008.1.8.4 Manually operated flush bolts or surface bolts are not permitted. Remove two bolts from the door at the SW corner of the building ( near the restroom). |
| 05/18/2007 | VIOL - COMPRESSED GASES | NSPRENGE | Violation | IFC 3003.3.3 Compressed gas containers, cylindrers, and tanks shall be secured to prevent falling. Secure your helium tank in shop area. |
| 05/18/2007 | VIOL - FLAMMABLE LIQUIDS | NSPRENGE | Violation | IFC 3403.5.3 Individual containers, packages, and cartons shall be identified, marked, labeled and placarded in accordance with federal regulations and applicable state laws. Each 55 gallon drum containing oil, transmission fluid, freon, etc shall be labled with the appropriate hazard notification and contents name. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00974
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2007 | COMPL - REINSPECTION | NSPRENGE | Approved | All violations were ebated. |