Full Fire Inspection

Outstanding Inspections

Case Number: T07FR00974
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
05/18/2007 INSP - FULL NSPRENGE Correction Required
05/18/2007 VIOL - FIRE RESIST.RATED CONST NSPRENGE Violation IFC 703.1 The required fire resistance rating of fire resistive rated construction ashall be maintained. Repair the opening in the ceiling of the shop over restroom.
05/18/2007 VIOL - FIRE PROTECTION SYSTEMS NSPRENGE Violation IFC 906.2 Fire extinguishers shall be maintained. Have your fire extinguishers serviced annually and tagged for approval.
05/18/2007 VIOL - FIRE PROTECTION SYSTEMS NSPRENGE Violation IFC 906.7 Hand held portable fire extinguishers shall be installed on hangers or brackets supplied. Mount any fire extingushers that are not already on brackets. ( 3 pressurized water extinguishers).
05/18/2007 VIOL - MEANS OF EGRESS NSPRENGE Violation IFC 1008.1.8.4 Manually operated flush bolts or surface bolts are not permitted. Remove two bolts from the door at the SW corner of the building ( near the restroom).
05/18/2007 VIOL - COMPRESSED GASES NSPRENGE Violation IFC 3003.3.3 Compressed gas containers, cylindrers, and tanks shall be secured to prevent falling. Secure your helium tank in shop area.
05/18/2007 VIOL - FLAMMABLE LIQUIDS NSPRENGE Violation IFC 3403.5.3 Individual containers, packages, and cartons shall be identified, marked, labeled and placarded in accordance with federal regulations and applicable state laws. Each 55 gallon drum containing oil, transmission fluid, freon, etc shall be labled with the appropriate hazard notification and contents name.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00974
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/12/2007 COMPL - REINSPECTION NSPRENGE Approved All violations were ebated.