Status:

COMPLETE

Type:

INSPECTION

Entered Date:

05/15/2007

Applicant:

K-GAM EL CON LLC 1/2 & MAGNA

Description:

Full fire inspection done by Inspector John Bieg on 5/15/07. "A-2" / Restaurant.

Outstanding Inspections

Case Number: T07FR00961
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
05/15/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2 Remove all storage from the water heater closet.
05/15/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 508.5.4 Remove storage from obstructing the sprinkler system riser pipe and controll valves, located in the loading dock.
05/15/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 604.2.4 #1. Repair the emergency lighting unit located on the ceiling above the northwest side of the bar. #2. Repair the emergency lighting unit located on the wall by the dish station. #3. Repair the emergency lighting unit located above the bread racks. #4. Repair the emergency lighting unit located above table 6-1.
05/15/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5 Remove the extension cord through the ceiling by the break room.
05/15/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Repair the defective portable fire extinguisher located behind the dessert display.
05/15/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 903.3.3 The sprinkler head located in the break room shall not be obstructed.
05/15/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.2 The exit sign located above the exit door located in the loading dock shall be illuminated.
05/15/2007 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.3.3 Secure the compressed gas cylinders located in the water heater closet. A re-inspection is scheduled for 5/29/07

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00961
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/23/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 7/23/07. Inspector John Bieg.