Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

05/14/2007

Applicant:

MENLO PARK SHOPPING CENTER COMPANY

Description:

Full fire inspection done by Inspector John Bieg on 5/14/07. "B" / Restaurant.

Outstanding Inspections

Case Number: T07FR00957
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
05/14/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2 Remove storage from around the water heater in the back room.
05/14/2007 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 505.1 Comply with this code.
05/14/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.4.1 Remove the unapproved power tap located in the kitchen.
05/14/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5 Remove the extension cord located by the exit door in the kitchen.
05/14/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 #1. Service and tag the hood system. #2. Service and tag the class K portable fire extinguisher. A re-inspection is scheduled for 5/29/07.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00957
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/20/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 5/20/07.