Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

05/11/2007

Applicant:

BROADWAY POWER CENTER GROUP LLC

Description:

Full FPI conducted 4/25/07

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00938
Case Description: INSPECTION
Total Completed Inspections - 3
End Date Description Inspector Results Comments
05/11/2007 INSP - SELF INSPECTION PROGRAM DGREENLE Approved Business shall be placed on Tucson Fire Department's "Self-Inspection Program"
05/11/2007 COMPLIANCE DGREENLE Approved Slide-Bolt lock will be allowed on non-required rear exit with the following conditions: 1. A sign stating "NOT AN EXIT" affixed to the interior side of the door. The sign shall consist of letters having a principal stroke of not less than 0.75 inch wide and at least 6 inches high on a contrasting background. An additional sign shall be posted on the door leading from the public area to the non-public area of the business. 2. A sign stating "THIS DOOR BLOCKED" affixed to the exterior side of the door. The sign shall consist of letters having a principal stroke of not less than 0.75 inch wide and at least 6 inches high on a contrasting background, and shall be weatherproof.
05/11/2007 INSP - FULL DGREENLE Approved Sprinkler system inspected 2/07 Certificate of Occupancy shall be updated to indicate name change and shall be posted on the premesis.