Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T07FR00847
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
05/01/2007 INSP - FULL MWAINWRI Violation INSPECTED THE VASCULAR LAB, AHCCCS, EKG, SLEEP DISORDER, CHAPEL, LEARNING LAB, CAFETERIA, TECH MANAGEMENT, INPATIENT PHARMACY, INFECTION PREVENTION, AND ICU.
05/01/2007 VIOL - FIRE RESIST.RATED CONST MWAINWRI Violation 2003 IFC 703.1 1) CEILING TILE OUT IN CAFETERIA. 2) CEILING TILE MISSING IN CAFETERIA DISHWASHING AREA. MOLD WAS ALSO NOTED ON ONE CEILING TILE IN DISHWASHING AREA.
05/01/2007 VIOL - FIRE RESIST.RATED CONST MWAINWRI Violation 2003 IFC 703.1 ROOMS 333,331,326,329 HAVE SMALL HOLES IN WALLS AROUND EACH ROOM. ATTN: CHECK THE OTHER ROOMS AS THEY BECOME UNOCCUPIED.
05/01/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2003 IFC 904.11.6.3 BAFFLE MISSING IN KITCHEN HOOD SYSTEM OVER DEEP FAT FRYERS.
05/01/2007 VIOL - COMPRESSED GASES MWAINWRI Violation 2003 IFC 3004.1 CO2 BOTTLES INBASEMENT BELOW KITCHEN ARE UNSECURED IN SUPPLY ROOM.