Case: T07FR00847
Case Details
Entered Date:
05/01/2007
Applicant:
TMC FOUNDATION
Description:
FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T07FR00847
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/01/2007 | INSP - FULL | MWAINWRI | Violation | INSPECTED THE VASCULAR LAB, AHCCCS, EKG, SLEEP DISORDER, CHAPEL, LEARNING LAB, CAFETERIA, TECH MANAGEMENT, INPATIENT PHARMACY, INFECTION PREVENTION, AND ICU. |
05/01/2007 | VIOL - FIRE RESIST.RATED CONST | MWAINWRI | Violation | 2003 IFC 703.1 1) CEILING TILE OUT IN CAFETERIA. 2) CEILING TILE MISSING IN CAFETERIA DISHWASHING AREA. MOLD WAS ALSO NOTED ON ONE CEILING TILE IN DISHWASHING AREA. |
05/01/2007 | VIOL - FIRE RESIST.RATED CONST | MWAINWRI | Violation | 2003 IFC 703.1 ROOMS 333,331,326,329 HAVE SMALL HOLES IN WALLS AROUND EACH ROOM. ATTN: CHECK THE OTHER ROOMS AS THEY BECOME UNOCCUPIED. |
05/01/2007 | VIOL - FIRE PROTECTION SYSTEMS | MWAINWRI | Violation | 2003 IFC 904.11.6.3 BAFFLE MISSING IN KITCHEN HOOD SYSTEM OVER DEEP FAT FRYERS. |
05/01/2007 | VIOL - COMPRESSED GASES | MWAINWRI | Violation | 2003 IFC 3004.1 CO2 BOTTLES INBASEMENT BELOW KITCHEN ARE UNSECURED IN SUPPLY ROOM. |