Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

05/01/2007

Applicant:

MC DONALDS CORPORATION

Description:

Full fire inspection done by Inspector John Bieg on 5/1/07. "A-2" / Restaurant.

Outstanding Inspections

Case Number: T07FR00841
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
05/01/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 #1. Service and tag the class K fire extinguisher located in the kitchen. #2. Service and tag the BC extinguisher located outside the employee break room.
05/01/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3 Clean all hood systems and maintain records of cleanings. A re-inspection is scheduled for 5/15/07.
05/01/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 The exit door that leads to the play area shall not have a double keyed deadbolt. { Replace with a thumb turn deadbolt.}
05/01/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.2 #1. The exit sign located on the inside of the play area above east door shall be illuminated. #2. The exit sign located above the south exit door in the kitchen shall be fully illuminated.
05/01/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.2 The two exits located in the kitchen shall not be obstructed.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00841
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/23/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 5/23/07. Inspector John Bieg.