Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

04/26/2007

Applicant:

CITY OF TUCSON

Description:

Routine Inspection

Outstanding Inspections

Case Number: T07FR00815
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
02/02/2007 VIOL - BUILDING SVCS & SYSTEMS WCUMMING Correction Required Behind door # 411 in Pod # 2 the hot water heater exhaust piping is disconnected, allowing harmful exhaust (CO) and fumes into the building.
02/02/2007 VIOL - FIRE RESIST.RATED CONST WCUMMING Correction Required Behind door # 410 several ceiling tiles are missing.
02/02/2007 VIOL - FIRE PROTECTION SYSTEMS WCUMMING Correction Required The fire alarm system control panel is showing a trouble signal for classroom 300 as well as a main system trouble indication.
02/02/2007 VIOL - MEANS OF EGRESS WCUMMING Correction Required One or more emergency exitway lights were found to be inoperative. Repair or replaced as needed.
02/02/2007 VIOL - MEANS OF EGRESS WCUMMING Correction Required One or more exit signs were found to be inoperative when the test button was activated. Repair or replace as needed.
02/02/2007 VIOL - MEANS OF EGRESS WCUMMING Correction Required Stage chairs were found blocking the exit and exitway in front of door # 215B. All exits and exit ways shall be unobstructed at all times.
02/02/2007 VIOL - MEANS OF EGRESS WCUMMING Correction Required The exit sign for door # 217B is on the wrong side of the door. It is on the side the leads back into the stage, to a door that opens in, and to a door that is locked.