Full fire inspection done by Inspector John Bieg on 4/25/07. "A-2" / Restaurant.

Outstanding Inspections

Case Number: T07FR00809
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
04/26/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 #1. Service and tag all hood systems. #2. Service and tag all portable fire extinguishers.
04/26/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.6 #1. The class K fire extinguisher located in the kitchen shall not be obstructed. #2. The fire extinguisher in the kitchen by the ice cream machine shall not be obstructed.
04/26/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.9 The extinguisher located in the kitchen by the north egress door shall comply with this code. A re-inspection is scheduled for 5/9/07.
04/26/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 Remove the keyed deadbolt from the exit door located on the east wall. { Replace with a thumb turn deadbolt.}
04/26/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.3 The south exit door shall comply with this code.
04/26/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.5 #1. Repair the emergency lighting unit located by the southwest exit door. #2. Repair the emergency lighting unit located by the south exit door. #3. Repair the emergency lighting unit located by the northeast entrance to the play area.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00809
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/30/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 5/30/07. Inspector John Bieg.