Case: T07FR00804
Case Details
Entered Date:
04/25/2007
Applicant:
TUCSON SCHOOL DISTRICT NO 1
Description:
Routine Inspection
Outstanding Inspections
Case Number: T07FR00804
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 10
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
03/01/2007 | VIOL - PRECAUTION AGAINST FIRE | WCUMMING | Correction Required | Combustibles are being stored on or near the electrical service devices in the west mechanical room behind the kitchen. |
03/01/2007 | VIOL - BUILDING SVCS & SYSTEMS | WCUMMING | Correction Required | On the west side of the stage near the exit a ceiling light has an open junction box with exposed wiring. |
03/01/2007 | VIOL - FIRE RESIST.RATED CONST | WCUMMING | Correction Required | In the corridor outside of room # 35 are several missing ceiling panels. |
03/01/2007 | VIOL - FIRE RESIST.RATED CONST | WCUMMING | Correction Required | On the west side of the stage near the exit is a missing ceiling panel. |
03/01/2007 | VIOL - FIRE PROTECTION SYSTEMS | WCUMMING | Correction Required | A "K" class portable fire extinguisher shall be available and visible within 30' of the commercial kitchen extinguishing system. |
03/01/2007 | VIOL - FIRE PROTECTION SYSTEMS | WCUMMING | Correction Required | Portable fire extinguishers were found with the last test / service date of 2004. These extinguishers shall be serviced / tested annually. |
03/01/2007 | VIOL - FIRE PROTECTION SYSTEMS | WCUMMING | Correction Required | The portable fire extinguisher in room # 20 is empty. |
03/01/2007 | VIOL - MEANS OF EGRESS | WCUMMING | Correction Required | One or more exit signs were found to be inoperative. Repair or replace as needed. |
03/01/2007 | VIOL - MEANS OF EGRESS | WCUMMING | Correction Required | The second set of exits off the stage that leads into the MPR are blocked on both sides. All exits and exitways shall be clear of obstructions at all times. |