End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
03/01/2007 VIOL - PRECAUTION AGAINST FIRE WCUMMING Correction Required Combustibles are being stored on or near the electrical service devices in the west mechanical room behind the kitchen.
03/01/2007 VIOL - BUILDING SVCS & SYSTEMS WCUMMING Correction Required On the west side of the stage near the exit a ceiling light has an open junction box with exposed wiring.
03/01/2007 VIOL - FIRE RESIST.RATED CONST WCUMMING Correction Required In the corridor outside of room # 35 are several missing ceiling panels.
03/01/2007 VIOL - FIRE RESIST.RATED CONST WCUMMING Correction Required On the west side of the stage near the exit is a missing ceiling panel.
03/01/2007 VIOL - FIRE PROTECTION SYSTEMS WCUMMING Correction Required A "K" class portable fire extinguisher shall be available and visible within 30' of the commercial kitchen extinguishing system.
03/01/2007 VIOL - FIRE PROTECTION SYSTEMS WCUMMING Correction Required Portable fire extinguishers were found with the last test / service date of 2004. These extinguishers shall be serviced / tested annually.
03/01/2007 VIOL - FIRE PROTECTION SYSTEMS WCUMMING Correction Required The portable fire extinguisher in room # 20 is empty.
03/01/2007 VIOL - MEANS OF EGRESS WCUMMING Correction Required One or more exit signs were found to be inoperative. Repair or replace as needed.
03/01/2007 VIOL - MEANS OF EGRESS WCUMMING Correction Required The second set of exits off the stage that leads into the MPR are blocked on both sides. All exits and exitways shall be clear of obstructions at all times.